CO2 Sensor
| Article number | 006-1-0100 |
| Operating principle | Non-dispersive infrared (NDIR) |
| Measured gas | CO₂ |
| Measurement range | 0–10 000ppm |
| Accuracy | ±50 ppm ±3% of reading1 |
| Operating range RH | <85 % RH |
| Operation range °C | <50 °C |
| Warm-up time | 0s |
| Response time | 30s |
| Power supply | 3.05 - 5.5 V |
| Peak current | 100 mA |
| Average current | 1–30µA |
| Communication | I2C, UART |
| Outputs | Digital |
| Compliance | ANSI/ASHRAE Standard 62.1-2022, RESET Standard Grade B, WELL Building Standard® (WELL v2™) |
| Maintenance | Maintenance-free |
| Life expectancy | >15 years |
| Dimensions | 34 x 21 x 12 mm (L x W x H) |
| Weight | 5 g |
| Storage conditions | -40 – 70°C |